System ZZ-Fire protection plug NE

Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, optical fibre cables and conduits

System information

Approval Number ETA-12/0088
Fire resistance class EI
Fire resistance duration 30 , 60 , 90 , 120
Seal type Cable penetration seal
Seal opening round
Component Options flexible wall , rigid wall , rigid floor

System components

Designation Art. no. PU
ZZ-Foam plug NE show variants
Designation Diameter Art. no. PU
ZZ-Foam plug NE Ø 65 B02V02-0009
B02V04-0006
B02V20-0008
2
4
20
ZZ-Foam plug NE Ø 78 B02V02-0010
B02V04-0007
B02V20-0009
2
4
20
ZZ-Foam plug NE Ø 107 B02V02-0011
B02V04-0008
B02V20-0010
2
4
20
ZZ-Foam plug NE Ø 122 B02V02-0012
B02V04-0009
B02V20-0011
2
4
20
ZZ-Foam plug NE Ø 134 B02V02-0013
B02V04-0010
B02V20-0012
2
4
20
ZZ-Foam plug NE Ø 165 B02V02-0014
B02V20-0013
2
20
ZZ-Foam plug NE Ø 200 B02V02-0015
B02V10-0004
B02V20-0014
2
10
20
ZZ-Foam plug NE Ø 250 B02V02-0016
B02V10-0002
2
10
ZZ-Wrap NE B04N00-0004 1
ZZ-Mastic NE 310 ml B15N00-0013 1
Identification plate ETA B16H00-0051 1
Downloads
Description

Details

Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, optical fibre cables and conduits

Additional Information

Additional Information

Suitable for
  • Core holes up to 240 mm in diameter in rigid walls and floors
  • Through penetration firestop systems with frequently changing penetrating elements
Approved penetrating elements
  • Sheathed electrical cables, telecommunication cables, optical fibre cables up to a maximum outer diameter of 80 mm
  • Tied cable bundles up to a total diameter of 100 mm consisting of sheathed electrical cables, telecommunication cables, optical fibre cables with a maximum outer diameter of 21 mm (sealing of the interstices in the interior is not necessary)
  • Non-sheathed electrical cables up to a maximum outer diameter of 24 mm
  • Individual lines of steel or plastic conduit for control purposes up to a pipe outer diameter of 16 mm
  • Plastic conduits up to an outer diameter of 16 mm
  • Cable support systems (cable trays, cable racks, cable ladders) made of steel profiles can be routed through the penetration seal

Subscribe now