System ZZ-Fire protection silicone NE

Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, and optical fibre cables.

System information

Approval Number ETA-13/0123
Fire resistance class EI
Fire resistance duration 30 , 60 , 90 , 120
Seal type Joint seal
Seal opening angular , round , unregular
Component Options flexible wall , rigid wall , rigid floor

System components

Downloads
Description

Details

Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, and optical fibre cables.

Additional Information

Additional Information

Suitable for
  • Fast and easy sealing of component openings,
  • Small penetration seals
  • Openings that are difficult to access and irregular,
  • Penetration seals in the outdoor area
Approved penetrating elements
  • Sheathed electrical cables, telecommunication cables, and optical fibre cables up to a maximum outer diameter of 21 mm