System ZZ-Fire protection block 200 NE

Mixed penetration seal to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables and optical fibre cables, conduits, as well as flammable and non-flammable pipes

System information

Approval Number ETA-10/0431
Fire resistance class EI
Fire resistance duration 30 , 60 , 90 , 120
Seal type Mixed penetration seal
Seal opening angular
Component Options flexible wall , rigid wall , rigid floor

System components

Designation Art. no. PU
ZZ-Foam block 200 NE show variants
Designation length Art. no. PU
ZZ-Foam block 200 NE 200 B01V01-0004
B01V04-0003
B01V18-0001
1
4
18
ZZ-Foam block 200 NE, vacuum-packed show variants
Designation length Art. no. PU
ZZ-Foam block 200 NE, vacuum-packed 200 B01V02-0003
B01V07-0001
2
7
ZZ-Foam block 200 NE, silicone coated show variants
Designation length Art. no. PU
ZZ-Foam block 200 NE, silicone coated 200 B01V04-0007
B01V18-0003
4
18
ZZ-Fire protection foam 2K NE 380 ml, 6-cartridge set B15N01-0106 1
ZZ-Wrap NE B04N00-0004 1
Downloads
Description

Details

Mixed penetration seal to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables and optical fibre cables, conduits, as well as flammable and non-flammable pipes

Additional Information

Additional Information

Suitable for
  • Medium-sized and large penetration seals with a medium to high density of penetrating elements
  • Through penetration firestop systems with frequently changing penetrating elements
Approved penetrating elements
  • Sheathed electrical cables, telecommunication cables, optical fibre cables up to an outer diameter of 80 mm
  • Tied cable bundles up to a total diameter of 100 mm consisting of sheathed electrical cables, telecommunication cables, optical fibre cables with a maximum outer diameter of 21 mm (sealing of the interstices in the interior is not necessary)
  • Non-sheathed electrical cables up to a maximum outer diameter of 24 mm
  • Individual lines of steel or plastic conduit for control purposes up to a pipe outer diameter of 16 mm
  • Cable support systems (cable trays, cable racks, cable ladders) made of steel profiles can be routed through the penetration seal
  • Plastic conduits up to an outer diameter of 40 mm, bundles of several pipes up to an outer diameter of 80 mm
  • Flammable pipes (without additional fire protection collars) with a pipe outer diameter up to 50 mm and pipe wall thicknesses from 1.8 mm to 5.6 mm (see ETA-10/0431 for pipe diagrams)
  • Non-flammable pipes of steel, stainless steel, cast steel and copper with a pipe outer diameter up to 88.9 mm and pipe wall thicknesses from 1.0 mm to 14.2 mm, pipes up to a diameter of 18mm can optionally be sealed without insulation (see ETA-10/0431 pipe diagrams)
  • Insulation of non-flammable pipes consisting of mineral wool shells (density ≥90 kg/m³) can either be routed through the penetration seal or can end on the surface of the sealing system (see ETA-10/0431 for application areas, insulation lengths and thicknesses,as well as pipe diagrams)
  • Rubber insulation AF /Armaflex of non-flammable pipes can be routed through the penetration seal (see ETA-10/0431 for application areas,insulation lengths and thicknesses, as well as pipe diagrams)
  • Combination possibility with ZZ-Fire protection foam 2K NE in areas with dense penetrating elements difficult accessibility