System No. C-AJ-0150

Blank opening in solid wall or floor

  • F-Rating: 2 h; T-Rating: 2 h
  • Maximum opening size: 384 in.┬▓ with a max. dimension of 32 in.
  • Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
  • Fire Protection Sealant ZZ 365 or Fire Protection Foam ZZ 360 to be filled between ZZ 260 and periphery of opening

Firestop products

Designation Art. no. PU
Fire Protection Block ZZ 260-8 B01V12-0001 12
Fire Protection Block ZZ 260-40 B06V03-0001 3
Fire Protection Sealant ZZ 365 B15V12-0001 12