System No. W-L-0046
Blank opening in drywall
- F-Rating: 2 h; T-Rating: 2 h
- Maximum opening size: 384 in.² with a max. dimension of 32 in.
- Fire rated gypsum board/ steel stud wall according to U400, V400 or W400 Series with minimum 2-1/2 in. wide studs
- Fire Protection Foam ZZ 360 to be filled between ZZ 260 and periphery of opening
Firestop products
Designation | Art. no. | PU |
---|---|---|
Fire Protection Foam ZZ 360, 6-cartridge set
incl. 12 mixing nozzles, 6 pairs of gloves, 1 roll of duct tape |
B15N01-0134 | 1 |