System No. C-AJ-3329

Cables in solid wall or floor

  • Power and control cables, telecommunication cables, optical fibre cables
  • F-Rating: 2 h; T-Rating: ½ h
  • Maximum 60% cable fill in opening of max. 5 in. diameter
  • Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
  • Optional: Steel sleeve grouted into floor or wall

Firestop products

Designation Art. no. PU
Fire Protection Plug ZZ 160
Designation Diameter Art. no. PU
ZZ 160-2.5 2.5 in B02V20-0015 20
ZZ 160-3 3 in B02V20-0016 20
ZZ 160-4 4 in B02V20-0017 20
ZZ 160-4.5 4.5 in B02V20-0018 20
ZZ 160-5 5 in B02V20-0019 20
ZZ 160-6 6 in B02V20-0020 20
ZZ 160-8 8 in B02V20-0021 20