Logo Close
Other country sites
Visit Website
Cable tray with cables in solid wall or floor | C-AJ-4105Cable tray with cables in solid wall or floor
Cable tray with cables in solid wall or floor | C-AJ-4105Cable tray with cables in solid wall or floor

System No. C-AJ-4105

Cable tray with cables in solid wall or floor

  • Up to 6 in. by 24 in. steel or aluminum cable tray with max. 45% cable fill
  • F-Rating: 2 h; T-Rating: 0 h
  • Maximum opening size: 384 in.┬▓ with a max dimension of 32 in.
  • Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
  • Annular space: point contact to max. 8 in.
  • Fire Protection Sealant ZZ 365 to be filled between cables, in voids between cables and ZZ 260 and between periphery of opening and ZZ 260

Firestop products

Designation Art. no. PU
Fire Protection Block ZZ 260-8 B01V12-0001 12
Fire Protection Block ZZ 260-40 B06V03-0001 3
Fire Protection Sealant ZZ 365 B15V12-0001 12