Logo Close
Other country sites
Visit Website
Mixed penetration seal in solid wall or floor | C-AJ-8233Mixed penetration seal in solid wall or floor
Mixed penetration seal in combination with Fire Protection Block ZZ 260 in solid wall or floor | C-AJ-8233Mixed penetration seal in combination with Fire Protection Block ZZ 260 in solid wall or floor
Mixed penetration seal in solid wall or floor | C-AJ-8233Mixed penetration seal in solid wall or floor
Mixed penetration seal in combination with Fire Protection Block ZZ 260 in solid wall or floor | C-AJ-8233Mixed penetration seal in combination with Fire Protection Block ZZ 260 in solid wall or floor

System No. C-AJ-8233

Mixed penetration seal in solid wall or floor

  • Cable bundle up to 4 in. diameter, metal pipes up to 4 in. diameter optionally glass fiber insulated
  • F-Rating: 2 h; T-Rating: 1/4 h, 1-1/4 h and 1-3/4 h
  • Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks

Fire Protection Foam ZZ 360 only

  • Max. opening size: 224 in.² with a max. dimension of 32 in.
  • Annular space: point contact to max. 3-1/2 in. (vertical) and 8 in. (horizontal)

In combination with Fire Protection Block ZZ 260

  • Max. opening size: 384 in.² with a max. dimension of 32 in.
  • Annular space: point contact to max. 3-1/2 in. (vertical) and 8 in. (horizontal) to periphery of opening or foam/block interface, rest of the opening has to be sealed with Fire Protection Block ZZ 260

Firestop products

Designation Art. no. PU
Fire Protection Foam ZZ 360, 6-cartridge set
incl. 12 mixing nozzles, 6 pairs of gloves, 1 roll of duct tape
B15N01-0134 1
Fire Protection Block ZZ 260-8 B01V12-0001 12
Fire Protection Block ZZ 260-40 B06V03-0001 3

Subscribe now