Mixed penetration seal in solid wall or floor | C-AJ-8234Mixed penetration seal in solid wall or floor
Mixed penetration seal in solid wall or floor | C-AJ-8234Mixed penetration seal in solid wall or floor

System No. C-AJ-8234

Mixed penetration seal in solid wall or floor

  • Cable bundle up to 4 in. diameter, metal pipes up to 4 in. diameter optionally glass fiber insulated
  • F-Rating: 2 h; T-Rating: 1/4 h, 1-1/2 h and 2 h
  • Max. opening size: 384 in.² with a max. dimension of 32 in.
  • Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
  • Annular space: point contact to max. 7-7/8 in.
  • Fire Protection Sealant ZZ 365 to be filled between cables, in voids between cables/ pipes and ZZ 260 and between periphery of opening and ZZ 260

Firestop products

Designation Art. no. PU
Fire Protection Block ZZ 260-8 B01V12-0001 12
Fire Protection Block ZZ 260-40 B06V03-0001 3
Fire Protection Sealant ZZ 365 B15V12-0001 12