System No. C-AJ-0150 Blank opening in solid wall or floor
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- ZZ® 365 Fire Protection Sealant or ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening
| Test norm | UL 1479 |
| Approval Number | C-AJ-0150 |
| Seal type | Blank Opening |
System components
| Designation | Art. no. | PU | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZZ® 260 Fire Protection Block show variants
| ||||||||||||||
ZZ® 365 Fire Protection Sealant show variants
| ||||||||||||||
Detailed information
- Downloads
- Description
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- ZZ® 365 Fire Protection Sealant or ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening