System No. C-AJ-0150 Blank opening in solid wall or floor
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- ZZ® 365 Fire Protection Sealant or ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening
System information
Test norm | UL 1479 |
Approval Number | C-AJ-0150 |
Seal type | Blank Opening |
System components
Designation | Art. no. | PU |
---|---|---|
ZZ® 260-8 Fire Protection Block | B01V12-0001 | 12 |
ZZ® 260-40 Fire Protection Block | B06N00-0018 | 4 |
ZZ® 365 Fire Protection Sealant | B15V12-0001 | 1 |
Detailed information
- Downloads
- Description
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- ZZ® 365 Fire Protection Sealant or ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening