System No. C-AJ-4105 Cable tray with cables in solid wall or floor
- Up to 6 in. by 24 in. steel or aluminum cable tray with max. 45% cable fill
- F-Rating: 2 h; T-Rating: 0 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: point contact to max. 8 in.
- ZZ® 365 Fire Protection Sealant to be filled between cables, in voids between cables and ZZ® 260 Fire Protection Block and between periphery of opening and ZZ® 260 Fire Protection Block
| Test norm | UL 1479 |
| Approval Number | C-AJ-4105 |
| Seal type | Mixed penetration seal |
System components
| Designation | Art. no. | PU | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZZ® 260 Fire Protection Block show variants
| ||||||||||||||
ZZ® 365 Fire Protection Sealant show variants
| ||||||||||||||
Detailed information
- Downloads
- Description
- Up to 6 in. by 24 in. steel or aluminum cable tray with max. 45% cable fill
- F-Rating: 2 h; T-Rating: 0 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: point contact to max. 8 in.
- ZZ® 365 Fire Protection Sealant to be filled between cables, in voids between cables and ZZ® 260 Fire Protection Block and between periphery of opening and ZZ® 260 Fire Protection Block