System No. C-AJ-3329 Cables in solid wall or floor
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 60% cable fill in opening of max. 5 in. diameter
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Optional: Steel sleeve grouted into floor or wall
| Test norm | UL 1479 |
| Approval Number | C-AJ-3329 |
| Seal type | Mixed penetration seal |
System components
| Designation | Art. no. | PU | ||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZZ® 160 Fire Protection Plug show variants
| ||||||||||||||||||||||||||
Detailed information
- Downloads
- Description
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 60% cable fill in opening of max. 5 in. diameter
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Optional: Steel sleeve grouted into floor or wall