ZZ® System No. C-AJ-3329 Cables in solid wall or floor
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 60% cable fill in opening of max. 5 in. diameter
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Optional: Steel sleeve grouted into floor or wall
System information
Test norm | UL 1479 |
Approval Number | C-AJ-3329 |
Seal type | Mixed penetration seal |
System components
Designation | Art.-Nr. | VE | ||||||||||||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Fire Protection Plug ZZ 160 show variants
|
Detailinformationen
- Downloads
- Description
Details
- Power and control cables, telecommunication cables, optical fibre cables
- F-Rating: 2 h; T-Rating: ½ h
- Maximum 60% cable fill in opening of max. 5 in. diameter
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
- Optional: Steel sleeve grouted into floor or wall
- Additional Information
Additional Information