System No. C-AJ-8233 Mixed penetration seal in solid wall or floor
- Cable bundle up to 4 in. diameter, metal pipes up to 4 in. diameter optionally glass fiber insulated
- F-Rating: 2 h; T-Rating: 1/4 h, 1-1/4 h and 1-3/4 h
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks
System information
Test norm | UL 1479 |
Approval Number | C-AJ-8233 |
Seal type | Mixed penetration seal |
System components
Designation | Art. no. | PU |
---|---|---|
ZZ® 260-40 Fire Protection Block | B06N00-0018 | 4 |
ZZ® 360 Fire Protection Foam, 6 pc.-set | B15N01-0134 | 1 |
Detailed information
- Downloads
- Description
- Cable bundle up to 4 in. diameter, metal pipes up to 4 in. diameter optionally glass fiber insulated
- F-Rating: 2 h; T-Rating: 1/4 h, 1-1/4 h and 1-3/4 h
- Floor or wall of min. 4-1/2 in. thick reinforced concrete or any UL Classified Concrete Blocks