System No. C-AJ-1642 Metallic pipe in solid wall or floor
- Copper pipes, steel pipes, iron pipes or steel conduits up to 4 in. diameter
- F-Rating: 2 h; T-Rating: ¼ h
- Max. diameter of opening is 5 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 2 ¼ in.
- Optional: Steel sleeve grouted into floor or wall
| Test norm | UL 1479 |
| Approval Number | C-AJ-1642 |
| Seal type | Pipe penetration seal |
System components
| Designation | Art. no. | PU | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
ZZ® 365 Fire Protection Sealant show variants
| ||||||||||
Detailed information
- Downloads
- Description
- Copper pipes, steel pipes, iron pipes or steel conduits up to 4 in. diameter
- F-Rating: 2 h; T-Rating: ¼ h
- Max. diameter of opening is 5 in.
- Floor or wall of min. 4 ½ in. thick reinforced concrete or any UL Classified Concrete Blocks
- Annular space: Point contact to max. 2 ¼ in.
- Optional: Steel sleeve grouted into floor or wall