ZZ® C10
Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, optical fibre cables and conduits
| Test norm | EN 1366-3 |
| Approval Number | ETA-12/0088 |
| Fire resistance class | E, EI |
| Fire resistance duration [min] | 90, 120 |
| Seal type | Cable penetration seal |
| Seal opening | round |
| approved components | flexible wall, rigid wall, rigid floor |
System components
| Designation | Art. no. | PU | ||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
ZZ® 130 Fire Protection Plug show variants
| ||||||||||||||||||||||||||||||||||||||
ZZ® 333 Fire Protection Mastic show variants
| ||||||||||||||||||||||||||||||||||||||
ZZ® 451-150 Fire Protection Wrap show variants
| ||||||||||||||||||||||||||||||||||||||
| Identification Plate ETA | B16H00-0051 | 1 | ||||||||||||||||||||||||||||||||||||
Detailed information
- Downloads
- Description
Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for electrical cables, telecommunication cables, optical fibre cables and conduits
- Additional Information
Suitable for - Core holes up to 240 mm in diameter in rigid walls and floors
- Through penetration firestop systems with frequently changing penetrating elements
Approved penetrating elements - Sheathed electrical cables, telecommunication cables, optical fibre cables up to a maximum outer diameter of 80 mm
- Tied cable bundles up to a total diameter of 100 mm consisting of sheathed electrical cables, telecommunication cables, optical fibre cables with a maximum outer diameter of 21 mm (sealing of the interstices in the interior is not necessary)
- Non-sheathed electrical cables up to a maximum outer diameter of 24 mm
- Individual lines of steel or plastic conduits for control purposes up to a pipe outer diameter of 16 mm
- Plastic conduits up to an outer diameter of 16 mm
- Cable support systems (cable trays, cable racks, cable ladders) made of steel profiles can be routed through the penetration seal
Maximum dimensions in rigid wall width x height [mm] Ø 240 Maximum dimensions in flexible wall width x height [mm] Ø 240 Maximum dimensions in rigid floor width x height [mm] Ø 240