ZZ® C30
Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for all types of sheathed cables except waveguides.
System information
| Test norm | EN 1366-3 |
| Approval Number | ETA-13/0093 |
| Fire resistance class | E, EI |
| Fire resistance duration [min] | 60, 90, 120 |
| Seal type | Cable penetration seal |
| Seal opening | angular, round, unregular |
| approved components | flexible wall, rigid wall, rigid floor |
System components
| Designation | Art.-Nr. | VE |
|---|---|---|
| ZZ® 333 Fire Protection Mastic | B15N00-0013 | 1 |
| Identification Plate ETA | B16H00-0051 | 1 |
Detailinformationen
- Downloads
- Description
Details
Cable penetration seal up to EI 120 for rigid walls, rigid floors and flexible walls. Through penetration firestop system for all types of sheathed cables except waveguides.
- Additional Information
Additional Information
Suitable for - Fast and easy sealing of component openings
- ZZ® 333 Fire Protection Mastic has a high level of stability
- Flammable backfill is possible
- Low filling depth
- Can be used in flexible wall without additional lining
Approved penetrating elements - Sheathed electrical cables, telecommunication cables, data cables and optical fibre cables except waveguides up to a maximum outer diameter of 21 mm
- Retrofitting of additional cables allowed
Maximum dimensions in rigid wall width x height [mm] 100x100 or Ø 113 Maximum dimensions in flexible wall width x height [mm] 100x100 or Ø 113 Maximum dimensions in rigid floor width x height [mm] 100x100 or Ø 113








![Glättspachtel 9 x 8,5 [cm] Glättspachtel 9 x 8,5 [cm]](/media/_processed_/1/a/csm_zz_spachtel_e3a788cc33.jpg)