System No. W-L-0046 Blank opening in drywall
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Fire rated gypsum board/ steel stud wall according to U400, V400 or W400 Series with minimum 2-1/2 in. wide studs
- ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening
System information
Test norm | UL 1479 |
Approval Number | W-L-0046 |
Seal type | Blank Opening |
System components
Designation | Art. no. | PU |
---|---|---|
ZZ® 260-8 Fire Protection Block | B01V12-0001 | 12 |
ZZ® 260-40 Fire Protection Block | B06N00-0018 | 4 |
ZZ® 360 Fire Protection Foam, 6 pc.-set | B15N01-0134 | 1 |
Detailed information
- Downloads
- Description
- F-Rating: 2 h; T-Rating: 2 h
- Max. opening size: 384 in.² with a max. dimension of 32 in.
- Fire rated gypsum board/ steel stud wall according to U400, V400 or W400 Series with minimum 2-1/2 in. wide studs
- ZZ® 360 Fire Protection Foam to be filled between ZZ® 260 Fire Protection Block and periphery of opening